TANGO
Device Server



FastVacuumValve
Device Attributes Description

FastVacuumValve Class

Revision: release_1_0_4 - Author: coquet

Scalar Attributes
Attribute name
Data Type
R/W Type
Expert
combinedState: combined boolean states of the valve // bit 0 : BSV_VS_Ouverte Valve opened // bit 1 : BSV_VS_Fermee Valve Closed // bit 2 : BSV_VS_Defaut Valve faulty // bit 3 : BSV_VS_Mouvement valve moving // bit 4 : BSV_Prete valve ready to close // bit 5 : BSV_VS_Defaut_Memorise memorized fault state // bit 6 : BSV_Interlocked valve closed on external interlock
DEV_SHORT
READ
No
maxClosingTime: maximum time for normal close operation. If move is longer, the valve falls in fault state. Read from RSV_Temps_max_fermeture Written in RSC_Temps_max_fermeture
DEV_DOUBLE
READ_WRITE
No
maxOpeningTime: maximum time for normal open operation. If move is longer, the valve falls in fault state. Read from RSV_Temps_max_ouverture Written in RSC_Temps_max_ouverture
DEV_DOUBLE
READ_WRITE
No
fault: true if fast valve is in fault
DEV_BOOLEAN
READ
No
memorizedFault: true if fast valve was in fault and not acknowledged
DEV_BOOLEAN
READ
No
isInterlocked: true if valve was closed on interlock
DEV_BOOLEAN
READ
No







ESRF - Software Engineering Group