Device Server |
|
|||||||||||||||||||||||||||
combinedState: combined boolean states of the valve // bit 0 : BSV_VS_Ouverte Valve opened // bit 1 : BSV_VS_Fermee Valve Closed // bit 2 : BSV_VS_Defaut Valve faulty // bit 3 : BSV_VS_Mouvement valve moving // bit 4 : BSV_Prete valve ready to close // bit 5 : BSV_VS_Defaut_Memorise memorized fault state // bit 6 : BSV_Interlocked valve closed on external interlock | |||||||||||||||||||||||||||
maxClosingTime: maximum time for normal close operation. If move is longer, the valve falls in fault state. Read from RSV_Temps_max_fermeture Written in RSC_Temps_max_fermeture | |||||||||||||||||||||||||||
maxOpeningTime: maximum time for normal open operation. If move is longer, the valve falls in fault state. Read from RSV_Temps_max_ouverture Written in RSC_Temps_max_ouverture | |||||||||||||||||||||||||||
fault: true if fast valve is in fault | |||||||||||||||||||||||||||
memorizedFault: true if fast valve was in fault and not acknowledged | |||||||||||||||||||||||||||
isInterlocked: true if valve was closed on interlock |