TANGO
Device Server



MOSTAB
Device Description

MOSTAB Class

Revision: release_1_0_1 - Author: sebleport
This device controls the MOSTAB SIS2900-LVPZT system designed by STRUCK. it uses a RS232 communication. a right wire is needed. the communication parameters are: - baud rate = 9600 - stop bit = 1 - parity = none - 8 data bits. Each frame has to be terminated by "LF" and "CR" characters (10 and 13 in decimal notation) frame exemples : - to return read only parameters : � RG � + LF + CR - to set the loop gain � S2=12.125 � + LF + CR 5 run modes are available: - 0 means " manual " - 1 means " Peak Search " - 2 means " Peak Hold " - 3 means " standby " - 4 means " Track set point " To change the run mode, use the SetRunMode(code) command and choose the corresponding number code



ESRF - Software Engineering Group