Device Properties |
Property name |
Property type |
Description |
CommProxy |
Tango::DEV_STRING |
Communication proxy device name.
For the Neslab Ex17 in RS-232 mode the Serial device must be configured in 19200 baud, 1 stop bit, no parity |
CommType |
Tango::DEV_LONG |
Communication interface type
0 = RS-232
1 = RS-485 |
CommAddr |
Tango::DEV_LONG |
Communication interface address
RS-232 : must be 1
RS-485 : address of the controller (0x01-0x64) on the bus |
EnableSecondSensor |
Tango::DEV_BOOLEAN |
|
PID |
Array of double |
PID[0] = control Proportionnal factor
PID[1] = control Integral time
PID[2] = control Differential time |