TANGO
Device Server



Timing Linac System
Device Attributes Description

TimingLinacSystem Class

Revision: release_1_0_3 - Author: langlois

Scalar Attributes
Attribute name
Data Type
R/W Type
Expert
spmLinacEvent: Event number for the Single Pulse Mode Linac channel
DEV_LONG
READ_WRITE
No
spmLinacTimeDelay: Static Delay in �s of the SPM linac channel
DEV_DOUBLE
READ_WRITE
No
spmLinacStepDelay: Static Delay in steps of the SPM linac channel
DEV_LONG
READ_WRITE
No
spmLinacTrigStatus: Status of the trigger: 1 -> OK 0 -> not OK
DEV_BOOLEAN
READ
No
mode: Set the mode: 1 - 4; corresponding to the number of pulse that will be genereted at each trigger of the board.
DEV_SHORT
READ_WRITE
No
clockMSStep: CLK_MS step value
DEV_DOUBLE
READ
No
clockRFStep: CLK_RF step value
DEV_DOUBLE
READ
No
receptionStatus: Reception failure: Fiber Optique status
DEV_BOOLEAN
READ
No
timingStatus: Timing status: defaut synchro
DEV_BOOLEAN
READ
No
temperature: Linac system's current temperature
DEV_DOUBLE
READ
Yes
ps2vValue: Current voltage on the 2V power supply
DEV_DOUBLE
READ
Yes
ps2vStatus: 2V power supply status
DEV_BOOLEAN
READ
Yes
ps3vValue: Current voltage on the 3V power supply
DEV_DOUBLE
READ
Yes
ps3vStatus: 3V power supply status
DEV_BOOLEAN
READ
Yes
ps3vpValue: Current voltage on the 3Vp power supply
DEV_DOUBLE
READ
Yes
ps3vpStatus: 3Vp power supply status
DEV_BOOLEAN
READ
Yes
ps6vValue: Current voltage on the 6V power supply
DEV_DOUBLE
READ
Yes
ps6vStatus: 6V power supply status
DEV_BOOLEAN
READ
Yes
psStatus: Global power supply status
DEV_BOOLEAN
READ
Yes
serialNumber: Serial number
DEV_LONG
READ
Yes
versionNumber: Version number
DEV_LONG
READ
Yes
revisionNumber: Revision number
DEV_LONG
READ
Yes
busNumber: Bus number
DEV_LONG
READ
Yes
slotNumber: Slot number
DEV_LONG
READ
Yes
rFrequency: Value of the RF Frequency set in the property of the device. put in an attribute only for archiving purpose.
DEV_DOUBLE
READ
Yes







ESRF - Software Engineering Group