States |
Names |
Descriptions |
ON |
Turbo pump is ON
If WSV_EtatPompe=1,2 or 3 |
OFF |
Turbo pump is OFF
If WSV_EtatPompe=0 |
FAULT |
The pump is in FAULT if DSV_EtatAlarmes <>1
Note: STATUS should show the folowwing text associated with 32 Alarms:
Bit number (not numerical value!) Alarm type
0 (LSB) No Error
1 (Not used)
2 (Not used)
3 RAM Error
4 Disturbance
5 Power failure
6 Overspeed
7 Overload
8 Controller OT
9 Pump Overtemp
10 Thermal Error
11 Driver RA
12 Driver OC
13 Driver OV
14 Driver UV
15 Driver HF
16 (Not used)
17 Tuning Error 1
18 Tuning Error 2
19 Tuning Error 3
20 Tuning Error 4
21 Tuning Error 5
22 Test Error
23 (Not used)
24 Cable Disconnect
25 Driver Error 1
26 Driver Error 2
27 Driver Error 3
28 Driver Error 4
29 Driver Error 5
30 Driver Error 6
31 (MSB) (Not used) |
UNKNOWN |
Communication is broken |