Device Properties |
Property name |
Property type |
Description |
Url |
Tango::DEV_STRING |
Device name of the PLC Server |
DBNumber |
Tango::DEV_LONG |
Device representative DataBlock number |
InputOffset |
Tango::DEV_LONG |
Input offset of the beginning of the data in the DB IN BYTES |
HardwarePollingTime |
Tango::DEV_LONG |
variables will be refreshed by hardware reading
every HardwarePollingTime.
given in : 1/10 sec.
example : 34 sec gives 3.4 sec between hardware reading accesses
Default : 10 ( 1 second |
InterlockTexts |
Array of string |
interlock text to be displayed in status field :
form :
BYTE_OFFSET.BIT_OFFSET:text associated with this bit
example :
....
0.7:flowmeter ANS_C01/VI/DEB.8 generated outgoing interlock
1.0:pirani gauge ANS_C01/VI/PI.5 generated an outgoing interlock
...
|
InterlocksPersistence |
Tango::DEV_LONG |
memorization of interlocks duration
given in : sec.
example : 3600 sec gives 1 hour persitence for memorized (disapeared) interlocks
Default : 86400 equals 24 hours |